Xanbus Automatic Generator Start Installation
Type 1
Type 1 is a three-wire GlowStop configuration recommended for “three-
wire” generators with glow plugs that need to be operated before a start is
attempted.
Figure 7
Type 1 Connection Diagram
Relay Function Preset Configuration Setting
Relay 1 mode GlowStop
Relay 3 mode No function
Gen Run signal hold time 0.5 s
Preheat time 20 s
Preheat to crank delay 1 s
Crank time 15 s
18
17
16
14
13
12
Relay 1
Relay 2
5Afuse
5Afuse
GENERATOR RUN SIGNAL
GENERATOR RUN SIGNAL RETURN
PREHEAT/STOP
START
AGS Harness Wires Generator Wires
For additional information, see “Circuit Limitations” on page 11.
Crank retry time 30 s
Gen Cool Down 30 s
Gen Spin Down 3 s
Shutdown bypass time 0 s
Start tries 3
Relay Function Preset Configuration Setting