Components and Architecture - Serial Ports (RS232 and RS485)
Revision 5 HC900 Hybrid Controller Installation and User Guide 19
9/03
Serial Ports (RS232 and RS485)
Overview
Ports configurable as ELN, Modbus RTU or Modbus TCP protocol.
Controller can act as Modbus master or slave through either port.
Controller can be master to slaves such as
Honeywell Operator Interface (1040, 559). Must be on 485 port. Will not work on 232 port with
232/485 converter.
Honeywell HC Designer PC software
Third party PC HMI software
Third party Operator Interface
Controller can slave to masters such as
Any Honeywell Modbus device (e.g., recorders, controllers, flame safety)
Any non-Honeywell Modbus device.
Only one master port at a time, can’t have RS232 and RS485 both as master ports.
For multiple slaves on RS232 port, a 232-to-485 converter is required.
Baud rates to 57,600
Table 2 shows the ways the two ports can be configured simultaneously.
Table 2 Simultaneous serial port configurations
See RS232 Port Configured as RS485 Port configured as
Figure 16 #1 ELN device* ELN device*
Figure 16 #2 Controller is Modbus Slave ELN device*
Figure 16 #6 Controller is one of multiple Modbus slaves** ELN device*
Figure 16 #3 ELN device* Controller is Modbus Slave
Figure 16 #4 Controller is Modbus Master to single slave ELN device*
Figure 16 #5
Controller is Modbus master to multiple
slaves**
ELN device*
Figure 17 #7 Controller is Modbus slave
Controller is Modbus master to multiple
slaves
Figure 17 #8
Controller is Modbus master to multiple
slaves
Controller is Modbus slave
Figure 17 #9 Controller is Modbus slave Controller is Modbus slave
Figure 17 #10 ELN device*
Controller is Modbus master to multiple
slaves
Figure 17 #11 Controller is Modbus slave via modem ELN device*
*Such as Honeywell HCDesigner configuration software running on a PC or Honeywell 1040/559 Operator Interface
**Requires RS232-RS485 converter