Specifications - HC900 Hybrid Controller Design
156 HC900 Hybrid Controller Installation and User Guide Revision 5
9/03
Specifications
HC900 Hybrid Controller Design
Controller Module
Feature
Description
CE Conformity (Europe)
This product is in conformity with the protection requirements of the following
European Council Directives: 73/23/EEC, the Low Voltage Directive, and 89/336/EEC,
the EMC Directive. Conformity of this product with any other “CE Mark” Directive(s)
shall not be assumed. EN61326: Electrical Equipment For Measurement, Control and
Laboratory use. EMC requirements.
Installation Category
(Over-voltage Category)
Category II: Energy-consuming equipment supplied from the fixed installation
(Multi-loop Process Controller). Local level appliances, and Industrial Control
Equipment. (EN 61010-1)
Pollution Degree
Pollution Degree 2: Normally non-conductive pollution with occasional conductivity
caused by condensation. (ref. IEC 664-1)
EMC Classification
Group 1, Class A, ISM Equipment
Product Classification
Class I: Fixed, Permanently Connected, Industrial Process Control Equipment with
protective earthing (grounding). (EN 61010-1)
Power, per rack
Controller Rack
Voltage: Universal power, 90 to 264 Vac, 47 to 63Hz
Rating: 130VA @ 264VAC, typical 110VA @ 115VAC
In-rush current: 7 amps peak-to-peak for 150 ms at 240 Vac
Variable; depends on I/O Module complement.