6.15.5 Serial Com Station Address
Press the MENU key to access the menu data screens. Press the Down arrow key to access
the Run/Switch select screen.
SER COM STATION ADDR
STATION ADDRESS: 31H
>*F1: DATA SET MODE
> Δ/: PRV/NEXT SCREEN
Press the F1 key to display the following active adjustment screen:
SER COM STATION ADDR
STATION ADDRESS: 31H
/: CHANGE DATA
>ENTER: ACCEPT CHANGE
6.15.6 Output Voltage Adjustment
While operating in the AC Input mode, press the MENU key for 4 seconds or more to display
the output voltage adjustment screen:
OUTPUT VOLT. ADJUST
OUTPUT VOLTAGE =###%
>F1: DATA SET MODE
> Δ/: PRV/NEXT SCREEN
Press the F1 key to display the following active adjustment screen:
OUTPUT VOLT. ADJUST
REFERENCE ADJUST: ##
/: CHANGE DATA
>ENTER: ACCEPT CHANGE
The fields marked ## will show the numerical value of the allowable voltage adjustment
parameter values. Press the Up/Down arrow keys to adjust the setting ±5 volts. This results in
a ±2 % change in the output voltage.
Attempts to adjust this setting while the inverter is not running will result in the following error
message:
OUTPUT VOLT. ADJUST
ADJUST PROHIBITED
DATA CANNOT CHANGE
> Δ/: PRV/NEXT SCREEN
4200 FA User’s Manual 47