17
Limitorque MX DeviceNet Field Unit FCD LMENIM2328-00 – 11/05
flowserve.com
An output is a signal produced at the PLC and sent to the actuator via the
network.
The user may select one output and one input instance.
The default assembly objects are as follows: Polled input - 105, Polled output - 100, Bitstrobe - 107,
COS - 109.
Table 4.1
Instance ID Type Data Component Name Size
100 Output Output 1 (All Control Channels) 9
101 Output Output 2 (Analog Control and ESD only) 5
102 Output Output 3 (Discrete Control and ESD only) 4
103 Output Output 4 (Analog Control only) 3
104 Output Output 5 (Discrete Control only) 3
105 Input Input 1 (All Status Information) 16
106 Input Input 2 (Position and Faults only) 6
107 Input Input 3 (Position and Faults only) 8
108 Input Input 4 (Position, User and Faults only) 11
109 Input Input 5 (Faults and Alarms only) 6
4.2 Output Assembly Instances
Table 4.2 – Output Assembly Instance 100
Assembly
Object
Instance ID
Data
Component
Name
Class
Instance
ID
Attribute
ID Name ID Name
Data
Type
100 Output 1 100 Channel
Interface
1 20 Ctrl_Status_Chan BYTE
100 Channel
Interface
1 1 AO_Ctrl_Valve_ Flow_Chan INT
100 Channel
Interface
1 9 DO_Position_Chan BYTE
100 Channel
Interface
1 21 DO_ESD_Poll_Cnxn BOOL
100 Channel
Interface
1 11 DO_Relay_Chan BYTE
100 Channel
Interface
1 18 DO_Move_Test_Chan BOOL
100 Channel
Interface
1 19 AO_Analog_Output_Chan UNIT
Table 4.3 – Output Assembly Instance 101
Assembly
Object
Instance ID
Data
Component
Name
Class
Instance
ID
Attribute
ID Name ID Name
Data
Type
101 Output 2 100 Channel
Interface
1 20 Ctrl_Status_Chan BYTE
100 Channel
Interface
1 1 AO_Ctrl_Valve_ Flow_Chan INT
100 Channel
Interface
1 21 DO_ESD_Poll_Cnxn BOOL
100 Channel
Interface
1 10 DO_Move_Test_Chan BOOL
•