Catalog No.: 2000.20P Effective: 12-1-07 Replaces: 4-1-05
Raytherm - Type H
Hydronic Heating Boilers Model 133
Indoor Outdoor Shipping Weight
Model
No.
Input MBTU
Output MBTU AFUE Output MBTU Lbs. (Approx.)
H-133 136 112 82.7% 109 160
NOTES:
Ratings shown are for elevations up to 2,000 feet. For elevations over 2,000 feet, reduce
ratings at the rate of 4% for each 1,000 feet above sea level.
BOILER RATE OF FLOW AND PRESSURE DROP
10°∆T 20°∆T 30°∆T 40°∆T
GPM
P FT.
GPM
P FT.
GPM
P FT.
GPM
P FT.
22 14.7 11 3.8 N/A N/A N/A N/A
Raypak, Inc. 2151 Eastman Avenue, Oxnard, CA 93030 (805) 278-5300 Fax (800) 872-9725 www.raypak.com