Page 1
INSTALLATION INSTRUCTIONS
SK0-0055-001 HUMIDISTAT
The humidistat is designed for
either return air duct or wall
mounting
. Packaged in a duct mount configuration,
(For this type
mounting begin installation at the section labeled return air duct
installation on page 2.)
for conversion to a wall mount configuration
simply pull off the knob and remove the mounting screws and rotate the
control 180° and reattach the mounting base, (For this type mounting
begin installation at the section labeled wall mount installation on
page 3.)
.
DANGER
∗
Do not cut or drill any air-conditioning or electrical
accessories during installation.
∗
Fatal electrocution is possible if you contact a live wire.
∗
Electrical power can cause electrical shock
∗
Disconnect all electrical power supplied to the equipment
before beginning installation.
∗
Blindness can occur if freon contacts your eyes.
CAUTION
∗
Do not install on any electrical system over 30 VAC
CAUTION
∗
All electrical wiring should comply with codes and
ordinances.
At Outside Temperatures Recommended Setting
-20°F -30°C 15%
-10°F -25°C 20%
0°F -20°C 25%
+10°F -10°C 30%
+20°F -5°C 35%
Over 20°F Over 0°C 40%
Recommended Settings
Warning:
Adjusting the
humidity control
higher than the rec-
ommended setting
may cause conden-
sation resulting in
possible damage to
the
home.