Circuit Overloading - Consideration should be given to the connection of the equipment
to the supply circuit and the effect that overloading of the circuits might have on over
current protection and supply wiring.
8.
Reliable Grounding - Reliable grounding of Rackmounted equipment should be
maintained. Particular attention should be given to supply connections other than direct
connections to the branch circuit (e.g., use of power strips).
9.
All AC and DC versions are intended for use in a Restricted Access Location (RAL
).
Wiring Instruction Guidelines for DC Module in 2DC and ACDC
1. Connection of a suitable grounding conductor to the grounding terminal at each
power supply module (a minimum 14AWG copper conductor should be
suitable based on a 15A circuit breaker requirement).
2. Connection of suitable supply wiring to the plus and minus terminals at each
power supply module (a minimum 14AWG copper conductors is considered
suitable based on the 11A input maximum). The input terminal block at the
power supply module is suitable for 22-14 AWG copper wire.
3. A suitable listed circuit breaker shall be provided in the building installation as
the unit's disconnect device. The branch circuit rating (i.e. minimum 15A listed
circuit breaker, etc.).
DC Power Supply Module Wiring Instructions
The following diagram shows the wiring configuration for a -48 VDC power supply module for
the 20-Slot Rackmount Chassis 2DC and ACDC.
NOTE
The chassis is protected against incorrect wiring configurations. When wired incorrectly, the
chassis will not function, but no damage will occur.